The Power Manager 345 is designed to provide power and mounting for a Tekmar Net 4 reset module. It can be used in applications that use Wiring Centers, or other zoning devices that require a single thermostat. This product provides a mounting enclosure, power for a Tekmar Net 4 Reset Module, and connects to one Tekmar Net 4 thermostat to control one zone pump.
Features
Powered 115 V auxiliary pump output Internal 56 VA transformer Tekmar Net 4 compatible CSA C US Certified for use in USA and Canada
Specifications:
Agency Approvals: CSA C US, meets Class B: ICES & FCC Part 15 Ambient Conditions: Indoor use only, 32 to 122 degrees F (0 to 50 degrees C), RH less than or equal to 80 percent to 88 degrees F (31 degrees C), down to 50 percent above 104 degrees F (40 degrees C), Altitude less than 6560 ft. (2000 m), Installation Category II, Pollution Degree Auxiliary Pump Inputs 24 V (ac) less than 0.5 VA Auxiliary Pump Relay: 115 V (ac) 5 A Combined Load: 11.5 A max Control Type: Microprocessor control, this is not a safety (limit) control Dimensions: 8-1/16 H x 11-1/8 W x 2-15/16 D (204 x 282 x 74 mm) Enclosure Material: Blue PC+ABS plastic with metal top and bottom conduit connection walls Enclosure NEMA Rating: NEMA 1 Power Supply: 115 V (ac) plus / minus 10 percent, 60 Hz, 12 A Transformer Power Available: 24 V (ac) 56 VA, fuse T2.5 A 250 V