Type |
How it works |
Where it is typically found |
Example |
|
Millivolt (standing pilot) |
A thermocouple or thermopile powers the valve from the pilot flame, so no line power is needed |
Older furnaces, gas water heaters, wall heaters |
|
|
Intermittent pilot |
A 24V valve with separate pilot and main coils; a spark lights the pilot on each call for heat and the main valve opens only after the pilot flame is proven |
Furnaces and boilers with electronic ignition |
|
|
Direct spark or hot surface ignition |
A 24V valve opens for a short trial for ignition, then a flame sensor must prove the flame |
Most modern furnaces |
|
|
Single-stage |
On or off, one firing rate |
Basic furnaces and boilers |
|
|
Two-stage |
Low fire at roughly 60 to 70% of capacity and high fire at 100% |
Two-stage furnaces |
|
|
Modulating |
Stepper motor or PWM actuator varies the firing rate |
High-efficiency modulating furnaces |
These are typical ranges from an HVAC training reference. The appliance data plate and manufacturer instructions always take priority.
|
Measurement (inches water column) |
Natural gas |
Propane (LP) |
|
Inlet pressure |
5 to 7 |
11 to 13 |
|
Single-stage or high fire manifold |
3.5 |
10.0 to 11.0 |
|
Two-stage low fire manifold |
1.5 to 1.9 |
4.5 to 5.0 |
Kit contents vary by appliance. As one example, a Trane furnace LP kit lists main burner orifices, a replacement spring for the first-stage regulator, a pressure tap adapter, an installer guide and warning labels. Always use the kit made for the exact furnace, boiler or water heater model. Kits on this page include the Goodman LPM-06 for two-stage furnaces and the Carrier KGAPN3901ALL for converting LP to natural gas.
|
Check |
Why it matters |
|
Appliance model and valve part number |
Both are printed on the data plate or valve body; valves are model specific |
|
Control voltage |
Millivolt, 24V and 120V valves are not interchangeable |
|
Inlet and outlet pipe size |
Fittings must match the gas line and manifold |
|
Fuel type and pressure |
Natural gas and propane use different orifices and regulator settings |
|
Ignition system |
Standing pilot, intermittent pilot and direct ignition valves are wired differently |
|
Term |
What it means |
|
Combination valve |
One body that holds the manual shutoff, two safety shutoff seats in series, the pressure regulator and the main operator |
|
Inlet and outlet size |
Pipe size at each port, written as inlet x outlet such as 3/4 x 3/4 or 1/2 x 1/2 |
|
Pressure regulator |
Holds the manifold pressure at the value on the appliance data plate; its spring is what a conversion kit changes |
|
Safety shutoff |
Redundant seats that close if the flame is lost or the control drops the call for heat |
|
Pilot and main coils |
Intermittent pilot valves have a pilot coil that opens first and a main coil that opens after the pilot flame is proven |
|
Slow opening |
Valve that opens the main seat gradually to give soft burner ignition |
These checks come from an HVAC service guide. Values vary by appliance, so confirm them against the manufacturer specifications, and only qualified technicians should test live gas equipment.
|
Check |
What it tells you |
|
24 to 28V AC between W and C during a call for heat (furnace) |
Confirms the control board is sending power to the valve |
|
No voltage at the valve |
Points to the control board, a safety switch or wiring, not the valve |
|
Coil resistance with power off and wires disconnected: about 40 to 70 ohms on a furnace, 40 to 80 ohms on a water heater |
An open reading means a burned out coil and a zero reading means a short |
|
Voltage present, good coil, no gas flow |
Points to a seized valve body |
|
Valve clicks but no gas flows |
Regulator failure or a blocked inlet |
|
Manifold pressure on a manometer: about 7 inches WC inlet and 3.5 inches WC outlet on a natural gas furnace |
An out of range difference suggests a regulator problem; high pressure shortens igniter and heat exchanger life, low pressure causes ignition trouble |
|
Water heater pilot will not stay lit after release |
Replace the thermocouple first; if the valve still will not hold, replace the combination valve |
A service guide lists these reasons to condemn a gas valve: gas leaking through the valve body and not just a fitting, the valve has been submerged, it is over 20 years old with visible degradation, a recall or service bulletin applies, or the body is physically damaged. A failed thermocouple or coil alone is not a reason to condemn the whole valve.
|
Situation |
Safe practice |
|
After any gas connection work |
Run a full leak check with a listed combustible gas detector, use soap solution as a second check on fittings, and do it before restoring power or lighting the appliance |
|
Shutting the gas off |
Use the appliance shutoff first; use the meter shutoff only for a confirmed leak or when the appliance shutoff cannot be reached |
|
Smell of gas |
Avoid switches and ignition sources, shut off the supply if safe, leave the building if the odor is strong and call the gas utility from outside |
|
Propane conversion |
Propane collects in low areas, so a gas detector is recommended in basements and confined spaces |
Valves are often replaced together with pilot assemblies or ignitors on the same appliance.