The Edwards SIGA-IB4 is a 4-inch detector mounting base with a built-in line fault isolator for Signature Series Class A signaling line circuits. The base isolates shorted segments by opening all isolators within 23 ms and then sequentially re-closing at 10 ms intervals to locate and seal the fault while maintaining loop operation. It mounts to common North American and European back boxes, accepts 12 to 18 AWG conductors (16 to 18 AWG preferred), and includes the SIGA-TS4 trim skirt. A compatible detector must be installed for isolator function; remote alarm LED is not supported.
Built-in SLC line fault isolator: opens within 23 ms on a short and recloses in 10 ms intervals to isolate faults
Mounting and wiring: fits 4-inch square, 1-gang, 3-1/2 and 4-inch octagon, BESA and 75 mm European boxes; accepts 12-18 AWG (16-18 preferred)
Construction and compatibility: high-impact engineering polymer housing, room-side screw terminals; compatible with Signature Series detector heads
Product Highlights
4-inch isolator detector base for Signature Series SLC with SIGA-TS4 trim skirt, room-side terminals, and fast fault isolation behavior
Isolator detector base / 4-inch detector mounting base
Series
Signature Series
Core Function
Built-in SLC line fault isolator for Class A circuits; opens on short and auto-restores via sequential reclosing
Loop/Protocol
Signature Series SLC
Compatibility
Compatible with Signature Series detector heads (SIGA-H2D, SIGA-HFS, SIGA-HRS, SIGA-PS, SIGA-IS, SIGA-IPHS)
Includes
SIGA-TS4 trim skirt
LED Support
Remote alarm LED not supported (SIGA-LED not supported)
Mounting
Fits 4-inch square, 1-gang, 3-1/2 and 4-inch octagon boxes, BESA, and 75 mm European boxes (60.3 mm centers)
Maximum wall-mount distance from ceiling
12 in (305 mm)
Wire Size
Accepts 12, 14, 16, or 18 AWG conductors (16 and 18 AWG preferred)
Terminals
Room-side accessible screw terminals; wiring terminals accept specified AWG; terminal assignments include DATA IN/OUT and DATA IN/OUT negative designations
Isolation response
Isolators open within 23 ms on a short; sequential reclosing occurs at 10 ms intervals starting from nearest loop controller
Fault isolation behavior
Opens to keep remainder of Class A SLC operating, then periodically re-energizes to restore service when fault clears
Construction
High-impact engineering polymer housing
Operating Range
32 to 120 F (0 to 49 C); 0 to 93% RH, non-condensing
Certifications
UL Listed (intelligent detector base with fault isolator)