The Edwards SIGA-IB is a Signature Series mounting base with a built-in line fault isolator designed for Class A signaling line circuits (SLC). The base opens isolators within 23 ms on a short and recloses sequentially in controlled 10 ms intervals to restore downstream power. It accepts 12 to 18 AWG conductors (16 and 18 AWG preferred), mounts to common North American and European back boxes, and provides room-side accessible screw terminals.
Built-in short-circuit isolator for Signature Series Class A SLC; opens within 23 ms and recloses sequentially in 10 ms intervals
Accepts 12â18 AWG wiring (16 and 18 AWG preferred) and fits 1-gang, 3.5â4 in octagon, and European/BESA boxes
Room-side accessible screw terminals; does not support SIGA-LED remote LED; addressable with built-in fan
Product Highlights
Signature Series isolator base for Class A SLC with 23 ms fault response, 12â18 AWG support, standard back-box mounting, and room-side terminals