Product Description
The TACO 334-T3 Dual Unit Valve automatically feeds water to a system when pressure drops below its set point. This combination unit integrates a boiler feed valve with an in-line pressure relief valve, factory set to 30 psi. Featuring a durable cast iron body and 1/2" threaded inlets, it maintains system pressure between 10 to 25 psi, suitable for heating applications. It also includes a built-in check to prevent system emptying.
- Adjustable operating pressure from 10 to 25 PSI.
- Built-in check prevents system emptying if incoming pressure fails.
- Features an exclusive lockable fast-fill lever.
Product Highlights
Combination boiler feed and pressure relief valve for automatic system water replenishment and pressure control.
Product Information
Standard Information
-
Brand: TACO
-
Manufacturer Part Number: TACO-334-T3
Technical Specifications
-
Inlet Connection: 1/2" Threaded (Union)
-
Outlet Connection: 1/2" Threaded
-
Operating Pressure Range: 10 to 25 psi
-
Material: Cast Iron
-
Application: Heating
-
Maximum Inlet Pressure: 100 PSI
-
Maximum Fluid Temperature: 212°F
-
Pressure Relief Valve Setting: 30 psi
-
Number of Ports: 2
-
Thread Type: National Pipe Thread (NPT)
-
Factory Setting (System Side): 12 psi