The SCHNEIDER ELECTRIC NQ430L2 is a Series NQ panelboard interior designed for lighting and distribution applications in commercial and industrial electrical systems. Rated for 225 amperes at 240 VAC or 48 VDC, this interior supports a 3-phase, 4-wire circuit configuration with a maximum of 30 circuits. It is compatible with QO and QOB main breaker types and features an aluminum bus. Licensed electricians install this interior into a matching NQ panelboard enclosure as part of a branch-circuit distribution assembly.
The NQ430L2 is suited for lighting and general distribution panels in commercial buildings, industrial facilities, and similar occupancies where a 225A, 3-phase, 4-wire distribution point is required. It fits NEMA 1 enclosures sized at 20 inches wide by 5.75 inches deep by 32 inches tall, and NEMA 3R, 5, or 12 enclosures sized at 20 inches wide by 6.5 inches deep by 32 inches tall. This interior ships as a single unit and is intended for installation by a qualified electrician in accordance with the NEC.
Designed for use with Series NQ panelboard enclosures in NEMA 1, NEMA 3R, NEMA 5, and NEMA 12 configurations. Accepts QO and QOB style main breakers. Specific enclosure and breaker compatibility should be verified against the Series NQ product documentation before installation.
Installation must be performed by a licensed electrician in accordance with the National Electrical Code (NEC) and all applicable local codes. De-energize and lock out the service entrance before handling any panelboard interior components. Verify that the enclosure dimensions and NEMA rating match the interior before mounting. Do not install breakers or terminate conductors until the interior is fully secured within the enclosure.
Thanks for subscribing!
This email has been registered!