The Potter PAD100-ZM is an addressable zone module that uses one address on an SLC loop to monitor two Class B initiating device circuits (IDCs) or one Class A IDC. It requires and supervises a 24 VDC auxiliary power connection from a Potter IPA series addressable panel or a Potter PSN series power supply. IDC wiring is field-selectable as Class B or Class A via an onboard DIP switch. A single red LED indicates normal polling and rapid flash on activation.
Monitors two Class B initiating device circuits or one Class A circuit using a single SLC address
Requires supervised 24 VDC auxiliary power from Potter IPA series panels or Potter PSN series power supplies
Field-selectable IDC wiring (Class A/Class B) via onboard DIP switch; single red LED indicates polling and activation
Product Highlights
Single-address SLC zone module for monitoring dual Class B or single Class A circuits with supervised 24 VDC power and DIP-switch selectable wiring.
Product Information
Standard Information
Brand: POTTER
Manufacturer Part Number: PAD100-ZM
Technical Specifications
Brand
POTTER
MPN
PAD100-ZM
Product Type
Addressable zone module
SLC Addresses Used
1 address
Monitored Circuits
Two Class B or one Class A initiating device circuits (IDCs)
Input Voltage
24 VDC auxiliary (supervised)
Power Source Compatibility
Potter IPA series addressable panel; Potter PSN series power supply
Circuit Configuration
Field-selectable Class A or Class B via onboard DIP switch
Indicator
One red LED (flashes during polling; rapid flash on activation)
Compatible Panels
Potter IPA series addressable panels; Potter AFC/ARC series (reported by some sources) [verify compatibility before installation]
Mounting Type
Standard 4 inch or double gang box
Wiring Gauge
Accepts 22 to 12 AWG
Dimensions
4.17 x 0.60 x 1.14 in
Addressing Notes
When monitoring two Class B inputs they appear as sub-points (e.g., 8.1, 8.2)
Listings/Certifications
UUKL listed for smoke control; CSFM approval (documents available)