Product Description
The Wilkins 12-375XL is a backflow preventer designed to protect potable water systems. This model uses a reduced pressure principle assembly for effective backflow prevention. The nominal size of this device is one half inch with female threaded connections at both ends. It features a durable and corrosion-resistant body made of reinforced nylon. The assembly is well-suited for applications involving health hazards in drinking water systems.
- Designed for health hazard applications
- Lead-free construction
- Meets numerous industry standards
Product Highlights
This unit is easy to install and maintain. The EZSwap pressure vessel allows for quick removal and flushing.
Product Information
Standard Information
-
Manufacturer: Wilkins
-
UPC: 612052075629
Technical Specifications
-
Type: Reduced Pressure Principle Assembly
-
Nominal Size: 1/2 Inch
-
End Connection: Female Threaded x Female Threaded
-
End to End Distance: 12-1/4 Inch
-
Body Material: Reinforced Nylon
-
Disc/Poppet Material: Silicone
-
Spring Material: 300 Series Stainless Steel
-
Seal Material: Silicone/Buna N
-
Temperature Rating: 180 Deg F
-
Pressure Rating: 175 PSI
-
Application: Health Hazard, Potable Water System
-
Applicable Standard: ASSE 1013, AWWA C511, ANSI B1.20.1, CSA B64.4, IAPMO, FDA, NSF/ANSI 61, CUPC
-
Lead-Free: Yes
-
Hydrostatic Test Pressure Rating: 350 PSI