Combination gas controls for use with hot surface/direct spark systems in 24 Vac, gas-fired appliances with capacities from 30 to 415 cfh. The VR8215 valve can be mounted in any orientation and the reduced installation turning radius makes it much easier to install.
- Controls include manual valve, two automatic operators, and pressure regulator.
- Provide two automatic valves that function independently, allowing one to act as a failsafe for the other.
- Solenoid operated first automatic valve opens on thermostat call for heat; closes when call for heat ends.
- Diaphragm operated second automatic valve opens under control of the regulator; closes if gas or power supply is interrupted.
- Meet codes requiring dual safety shutoff.
- Natural to LP and LP to Natural conversion kits available for standard and slow opening gas valves.
- ON-OFF lighting sequence.
- All adjustments, wiring connections and pilot outlet are accessible from top of control.