The CARRIER NPLPCONV013C00 Conversion Kit is designed to convert heating units to operate on propane gas. This kit supports both single-stage and two-stage furnace models, suitable for units with heating inputs ranging from 40,000 to 130,000 Btu/hr. It is intended for installations at standard altitudes of 0 to 2000 feet (0 to 610 meters). The kit includes components for orifice and burner insert replacement, ensuring proper gas valve adjustment for correct manifold pressure. It also features a low gas pressure switch for safety and optimal performance.

  • Converts heating units to propane gas operation
  • Supports single-stage and two-stage furnace models
  • Applicable for units with heating inputs from 40,000 to 130,000 Btu/hr

Product Highlights

This kit facilitates the conversion of heating units to propane gas, supporting a wide range of furnace models and heating inputs for standard altitude installations.

Product Information

Standard Information

  • Brand: CARRIER
  • Manufacturer Part Number: NPLPCONV013C00
Technical Specifications
Manufacturer
Carrier
MPN
NPLPCONV013C00
Standard Altitude
0-2000 ft
Compatible Single-Stage Models
PDD3, PDS3, PGD3, PDD4, PDS4, PGD4, PGD5, PGN4, PGN5, PGS3, PGS4, PGS5, WPG3**4, WPG4**4
Compatible Two-Stage Models
PGR5
Incompatible Models (Natural Gas Only)
PGD4********2, PGS4********2, PGR5 ********2, WPG4********U
Heating Input Range
40,000 to 130,000 Btu/hr
Minimum Propane Manifold Pressure
10.0 IN.WC
Propane Gas Supply Pressure
11.0 IN. WC to 13 IN. WC
Low Gas Pressure Switch Open
Less than 6.5 IN. WC
Low Gas Pressure Switch Close
Not more than 10.2 IN. WC
Catalog Number
IIK-NPLPCONV-01
Replaces Part Number
46206211402
INTERNATIONAL COMFORT PRODUCTS Carrier NPLPCONV013C00 Conversion Kit 40,000 to 130,000 Btu/hr Replaces 46206211402

Vendor: INTERNATIONAL COMFORT PRODUCTS

Carrier NPLPCONV013C00 Conversion Kit 40,000 to 130,000 Btu/hr Replaces 46206211402

$184.10

Vendor: INTERNATIONAL COMFORT PRODUCTS

Carrier NPLPCONV013C00 Conversion Kit 40,000 to 130,000 Btu/hr Replaces 46206211402

$184.10

Related Products

Customer Support Image

Need Support?

Call Jack and His Team