{"product_id":"kele-vti-2-p-v-i-transducer-24-vdc-panel-vti-2-p","title":"Kele VTI-2-P V\/I Transducer 24 VDC (Panel) VTI-2-P","description":"\u003ch3\u003eProduct Description\u003c\/h3\u003e\n\u003cp\u003eThe Kele VTI-2-P is a voltage\/current transducer that converts voltage, current, or potentiometer inputs into a 4-20 mA non-isolated signal and provides dual, independently configurable outputs. It accepts 1-19 VDC or 1.33-76 mA input ranges, is DC powered with a nominal 24 VDC supply (22-27 VDC half-wave), and can be configured direct or reverse acting. The unit is panel-mount with screw terminal wiring and LED input indication, intended for HVAC and building automation signal conversion and rescaling.\u003c\/p\u003e\n\u003cul\u003e\n  \u003cli\u003eConverts 1-19 VDC or 1.33-76 mA inputs to 4-20 mA outputs with loss-of-input resulting in 0 mA\u003c\/li\u003e\n  \u003cli\u003eSingle input with dual independently configurable 4-20 mA outputs; direct or reverse acting; linearity \u0026lt;1% of span\u003c\/li\u003e\n  \u003cli\u003e24 VDC nominal supply (22-27 VDC half-wave), panel mount enclosure, screw terminal wiring, LED indication of valid input\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003ch4\u003eProduct Highlights\u003c\/h4\u003e\n\u003cp\u003eDual independent 4-20 mA outputs; accepts 1-19 VDC or 1.33-76 mA inputs; nominal 24 VDC supply; panel mount with screw terminals\u003c\/p\u003e\n\u003ch3\u003eProduct Information\u003c\/h3\u003e\n\u003ch4\u003eStandard Information\u003c\/h4\u003e\n\u003cul\u003e\n  \u003cli\u003e\n\u003cstrong\u003eBrand\u003c\/strong\u003e: KELE\u003c\/li\u003e\n  \u003cli\u003e\n\u003cstrong\u003eManufacturer Part Number\u003c\/strong\u003e: VTI-2-P\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003ch4\u003eTechnical Specifications\u003c\/h4\u003e\n\u003cul\u003e\n  \u003cli\u003e\n\u003cstrong\u003eBrand\u003c\/strong\u003e: Kele\u003c\/li\u003e\n  \u003cli\u003e\n\u003cstrong\u003eManufacturer Part Number\u003c\/strong\u003e: VTI-2-P\u003c\/li\u003e\n  \u003cli\u003e\n\u003cstrong\u003eType\u003c\/strong\u003e: Universal Analog Converter \/ V\/I Transducer\u003c\/li\u003e\n  \u003cli\u003e\n\u003cstrong\u003eInput Signal\u003c\/strong\u003e: Voltage, current, or potentiometer\u003c\/li\u003e\n  \u003cli\u003e\n\u003cstrong\u003eInput Range (Voltage)\u003c\/strong\u003e: 1-19 VDC (1 V minimum span)\u003c\/li\u003e\n  \u003cli\u003e\n\u003cstrong\u003eInput Range (Current)\u003c\/strong\u003e: 1.33-76 mA\u003c\/li\u003e\n  \u003cli\u003e\n\u003cstrong\u003eInput Loss Threshold\u003c\/strong\u003e: 0.7 VDC\u003c\/li\u003e\n  \u003cli\u003e\n\u003cstrong\u003eInput Impedance\u003c\/strong\u003e: 150 kOhm @ 1-19 VDC; 250 Ohm @ 4-40 mA (4 mA min span); 500 Ohm @ 2-38 mA (2 mA min span); 750 Ohm @ 1.3-25 mA (1.33 mA min span)\u003c\/li\u003e\n  \u003cli\u003e\n\u003cstrong\u003eOutput Signal\u003c\/strong\u003e: 4-20 mA analog (non-isolated)\u003c\/li\u003e\n  \u003cli\u003e\n\u003cstrong\u003eOutput Current\u003c\/strong\u003e: 4-20 mA\u003c\/li\u003e\n  \u003cli\u003e\n\u003cstrong\u003eOutput Voltage (Reference)\u003c\/strong\u003e: 10 VDC @ 15 mA max (for 1-19 VDC input); 6 VDC @ 10 mA max (for 1-11 VDC input)\u003c\/li\u003e\n  \u003cli\u003e\n\u003cstrong\u003eOutput Burden\u003c\/strong\u003e: 850 Ohm maximum @ 24 VDC; Rmax = (Vsupply - 7) \/ 20 mA\u003c\/li\u003e\n  \u003cli\u003e\n\u003cstrong\u003eOutputs\u003c\/strong\u003e: Dual, independently configurable\u003c\/li\u003e\n  \u003cli\u003e\n\u003cstrong\u003eSupply Voltage (Nominal)\u003c\/strong\u003e: 24 VDC\u003c\/li\u003e\n  \u003cli\u003e\n\u003cstrong\u003eSupply Voltage (Range\/Series)\u003c\/strong\u003e: 22-27 VDC, half-wave\u003c\/li\u003e\n  \u003cli\u003e\n\u003cstrong\u003eAction\u003c\/strong\u003e: Direct or reverse acting\u003c\/li\u003e\n  \u003cli\u003e\n\u003cstrong\u003eLinearity\u003c\/strong\u003e: \u0026lt;1% of span\u003c\/li\u003e\n  \u003cli\u003e\n\u003cstrong\u003eWiring Terminations\u003c\/strong\u003e: Screw terminals\u003c\/li\u003e\n  \u003cli\u003e\n\u003cstrong\u003eMounting Type\u003c\/strong\u003e: Panel\u003c\/li\u003e\n  \u003cli\u003e\n\u003cstrong\u003eOperating Temperature\u003c\/strong\u003e: 32 to 158 F (0 to 70 C)\u003c\/li\u003e\n  \u003cli\u003e\n\u003cstrong\u003eOperating Humidity\u003c\/strong\u003e: 5% to 95% RH (non-condensing)\u003c\/li\u003e\n  \u003cli\u003e\n\u003cstrong\u003eApprovals\u003c\/strong\u003e: RoHS\u003c\/li\u003e\n\u003c\/ul\u003e\n","brand":"KELE","offers":[{"title":"Default Title","offer_id":51407498412338,"sku":"VTI-2-P","price":227.43,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0270\/4519\/9983\/files\/313044385.jpg?v=1782978302","url":"https:\/\/voomisupply.com\/products\/kele-vti-2-p-v-i-transducer-24-vdc-panel-vti-2-p","provider":"Voomi Supply","version":"1.0","type":"link"}