{"product_id":"honeywell-c7262a1016-co2-temp-sensor","title":"Honeywell C7262A1016 CO2 \/Temp Sensor","description":"\u003ch3\u003eProduct Description\u003c\/h3\u003e\n\u003cp\u003eThe HONEYWELL C7262A1016 is a stand-alone carbon dioxide (CO2) and temperature sensor for use in determining ventilation necessity with HVAC controllers. It measures CO2 concentration and temperature to control the amount of fresh outdoor air supplied. Designed for wall mounting, it utilizes NDIR technology for accurate CO2 level measurement.\u003c\/p\u003e\n\u003cul\u003e\n  \u003cli\u003eUsed for CO2 based ventilation control.\u003c\/li\u003e\n  \u003cli\u003eIntegral 20K ohm NTC temperature output\u003c\/li\u003e\n  \u003cli\u003eNon-Dispersion-Infrared (NDIR) technology used to measure carbon dioxide gas.\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003ch4\u003eProduct Highlights\u003c\/h4\u003e\n\u003cp\u003eThe C7262A1016 sensor helps ensure a comfortable, productive, and safe environment for workers and occupants.\u003c\/p\u003e\n\u003ch3\u003eProduct Information\u003c\/h3\u003e\n\u003ch4\u003eStandard Information\u003c\/h4\u003e\n\u003cul\u003e\n  \u003cli\u003e\n\u003cstrong\u003eBrand\u003c\/strong\u003e: HONEYWELL\u003c\/li\u003e\n  \u003cli\u003e\n\u003cstrong\u003eManufacturer Part Number\u003c\/strong\u003e: C7262A1016\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003ch4\u003eTechnical Specifications\u003c\/h4\u003e\n\u003cul\u003e\n  \u003cli\u003e\n\u003cstrong\u003eItem Number\u003c\/strong\u003e: C7262A1016\u003c\/li\u003e\n  \u003cli\u003e\n\u003cstrong\u003eBrand\u003c\/strong\u003e: Honeywell\u003c\/li\u003e\n  \u003cli\u003e\n\u003cstrong\u003eMount\u003c\/strong\u003e: Wall\u003c\/li\u003e\n  \u003cli\u003e\n\u003cstrong\u003eVoltage\u003c\/strong\u003e: 24V\u003c\/li\u003e\n  \u003cli\u003e\n\u003cstrong\u003eSensor Type\u003c\/strong\u003e: Non-dispersive infrared (NDIR)\u003c\/li\u003e\n  \u003cli\u003e\n\u003cstrong\u003eRelay\u003c\/strong\u003e: Yes\u003c\/li\u003e\n  \u003cli\u003e\n\u003cstrong\u003eOutput Type\u003c\/strong\u003e: V or mA\u003c\/li\u003e\n  \u003cli\u003e\n\u003cstrong\u003eDisplay\u003c\/strong\u003e: 4-Digit LCD\u003c\/li\u003e\n  \u003cli\u003e\n\u003cstrong\u003eMeasurement Range\u003c\/strong\u003e: 0-2000 ppm \t5% and \t50 ppm\u003c\/li\u003e\n  \u003cli\u003e\n\u003cstrong\u003eApplication\u003c\/strong\u003e: Greenhouse,Laboratory,Food \u0026amp; Beverage,IAQ,Parking Garage,Agricultural\u003c\/li\u003e\n  \u003cli\u003e\n\u003cstrong\u003eOutput Signal\u003c\/strong\u003e: Current\u003c\/li\u003e\n  \u003cli\u003e\n\u003cstrong\u003eSupply Voltage\u003c\/strong\u003e: 24 VAC \t20% @ 3 VA, 50\/60 Hz; 24 VDCAC \t20% @ 125 mA\u003c\/li\u003e\n  \u003cli\u003e\n\u003cstrong\u003eAccuracy\u003c\/strong\u003e: 30 ppm + 2% of reading\u003c\/li\u003e\n  \u003cli\u003e\n\u003cstrong\u003eSignal Output\u003c\/strong\u003e: 0\/2-10 VDC @ 5k\t, 0\/ 4-20 mA @ 500\t, (jumper selectable)\u003c\/li\u003e\n  \u003cli\u003e\n\u003cstrong\u003ePressure Dependence\u003c\/strong\u003e: 1.4% change in reading per 0.15 psig (1.0 kPa) deviation from 14.5 psig (1000 kPa)\u003c\/li\u003e\n  \u003cli\u003e\n\u003cstrong\u003eCalibration Interval\u003c\/strong\u003e: Five years\u003c\/li\u003e\n  \u003cli\u003e\n\u003cstrong\u003eResponse Time\u003c\/strong\u003e: 2 minutes\u003c\/li\u003e\n  \u003cli\u003e\n\u003cstrong\u003eRelay Output\u003c\/strong\u003e: Shipped N.O., close at 800 ppm (selectable) Contact rating: 1A @ 50 VAC\/24 VDC Minimum load: 1mA @ 5 VDC, SPST, (100 ppm DIF)\u003c\/li\u003e\n  \u003cli\u003e\n\u003cstrong\u003eWiring Terminations\u003c\/strong\u003e: 20 AWG, 8\" cable, 20 AWG, 6\" cable\u003c\/li\u003e\n  \u003cli\u003e\n\u003cstrong\u003eOperating Temperature\u003c\/strong\u003e: 32\t to 122\tF (0\t to 50\tC)\u003c\/li\u003e\n  \u003cli\u003e\n\u003cstrong\u003eOperating Humidity\u003c\/strong\u003e: 0% to 95% RH noncondensing\u003c\/li\u003e\n  \u003cli\u003e\n\u003cstrong\u003eEnclosure Rating\u003c\/strong\u003e: Wall: NEMA 1\u003c\/li\u003e\n  \u003cli\u003e\n\u003cstrong\u003eConfiguration\u003c\/strong\u003e: Room\u003c\/li\u003e\n  \u003cli\u003e\n\u003cstrong\u003eEnclosure\u003c\/strong\u003e: Plastic\u003c\/li\u003e\n  \u003cli\u003e\n\u003cstrong\u003eMounting\u003c\/strong\u003e: Wall Mount\u003c\/li\u003e\n  \u003cli\u003e\n\u003cstrong\u003eOutput Voltage Signal Range\u003c\/strong\u003e: 2 To 10 V, 4 To 20 mA\u003c\/li\u003e\n  \u003cli\u003e\n\u003cstrong\u003eTemperature Sensor Type\u003c\/strong\u003e: 20K\u003c\/li\u003e\n  \u003cli\u003e\n\u003cstrong\u003eSensors Application\u003c\/strong\u003e: Gas Specialty\u003c\/li\u003e\n\u003c\/ul\u003e\n","brand":"HONEYWELL","offers":[{"title":"Default Title","offer_id":51161795100978,"sku":"C7262A1016","price":898.02,"currency_code":"USD","in_stock":false}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0270\/4519\/9983\/files\/306250082.jpg?v=1778882095","url":"https:\/\/voomisupply.com\/products\/honeywell-c7262a1016-co2-temp-sensor","provider":"Voomi Supply","version":"1.0","type":"link"}